031 01973 000 031 01933 000 Oem York Coleman Luxaire Furnace Control Board

031 01973 000 031 01933 000 Oem York Coleman Luxaire Furnace Control Board

031 01973 000 031 01933 000 OEM York Coleman Luxaire Furnace Control Board

PARTS LIST1. Ignition control P N 331030100002. Installation Instruction SheetINSTALLATION OF IGNITION CONTROL1. Orient the control as close as possible to the orientation of the board being replaced. 2. Align the plastic mounting feet with the mounting holes in the electric panel and press on each corner of the control board to seat the mounting feet. 3. Figure 2 shows a typical system wiring diagram which may vary slightly depending on the furnace model. Use the wiring diagram label on the furnace as your primary guide. 4. Check to see that all wire connections were made properly before applying power. 5. Apply power and test furnace operation. FURNACE CONTROL DIAGNOSTICSThe furnace has built in self diagnostic capability. If a system problem occurs a blinking LED can flash red green or amber to indicate various conditions. The control continuously monitors its own operation and the operation of the system. If a failure occurs the LED will indicate the failure code. If the failure is internal to the control the light will stay on continuously. In this case the entire control should be replaced as the control is not field repairable. Flash sequence codes 1 through 11 are as follows: LED will turn €œon € for 1 4 second and €œoff € for 1 4 second. This pattern will be repeated the number of times equal to the code. For example six €œon € flashes equals a number 6 fault code. All flash code sequences are broken by a 2 second €œoff € period. SLOW GREEN FLASH: Normal operation. SLOW AMBER FLASH: Normal operation with call for heat. RAPID RED FLASH: Twinning error incorrect 24V phasing. Check twinning wiring. RAPID AMBER FLASH: Flame sense current is below 1. 5 microamps. Check and clean flame sensor. Check for propergas flow. Verify that current is greater than 1. 5 microamps at flame current test pad. 4 AMBER FLASHES: The control is recieving a €œY € signal from the thermostat without a €œG € signal indicating improper thermostat wiring. 1RED FLASH: This indicates that flame was sensed when there was not a call for heat. The control will turn on both the inducer motor and supply air blower. A gas valve that leaks or is slow closing would typically cause this fault. 2 RED FLASHES: This indicates that the normally open pressure switch contacts are stuck in the closed position. The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring. 3 RED FLASHES: This indicates the normally open pressure switch contact did not close after the inducer was energized. This could be caused by a number of problems: faulty inducer blocked vent pipe broken pressure switch hose or faulty pressure switch. 4 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts. The control will operate the supply air blower and inducer. This condition maybe caused by: dirty filter improperly sized duct system incorrect blower speed setting incorrect firing rate or faulty blower motor. Also this fault code could be caused by a blown fuse located on the control board. 5 RED FLASHES: This fault is indicated if the normally closed contacts in the rollout switch opens. The rollout control is manually reset. If it has opened check for proper combustion air proper inducer operation and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power 24 VAC to the control after correcting the failure condition. Also this fault code could be caused by a blown fuse located on the control board. 6 RED FLASHES: This indicates that after the unit was operating the pressure switch opened 4 times during the call for heat. If the main blower is in a €œDelay on € mode it will complete it and any subsequent delay off period. The furnace will lock out for one hour and then restart. 7 RED FLASHES: This fault code indicates that the flame could not be established. This no light condition occurred 3 times 2 retries during the call for heat before locking out. Low gas pressure faulty gas valve dirty or faulty flame sensor faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart. 8 RED FLASHES: This fault is indicated if the flame is lost 5 times 4 recycles during the heating cycle. This could be caused by low gas pressure dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart. 9 RED FLASHES: Indicates reversed line voltage polarity or grounding problem. Both heating and cooling operations will be affected. Check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis. 10 RED FLASHES: Gas flow with no call for heat. Check gas valve and gas valve wiring. 11 RED FLASHES: This indicates that a primary or auxiliary limit switch has opened its normally closed contacts and has remained open for more than five minutes. This condition is usually caused by a failed blower motor or blower wheel. Cycle power 24 VAC to the control to reset the hard lockout condition after correcting the failure condition. 12 RED FLASHES: This code indicates an open igniter circuit which could be a disconnected or loose wire or a cracked or broken igniter. STEADY ON RED: Control failure. Replace control board. 60 MINUTE AUTOMATIC RESET FROM LOCKOUT: This control includes a €œwatchdog € type circuit that will reset from a lockout condition after 60 minutes. Operational faults 678 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation. When the gas pressure is restored at some point the €œwatchdog € would restart the unit and provide heat for the house. If a flame is detected the control flashes the LED for 1 8 of a second and then enters a flame stabilization period.

Price: $92.99

Explore Deals for: 031 01973 000 031 01933 000 OEM York Coleman Luxaire Furnace Control Board

error

You can share this page here :)